Free Gas Pipe Sizing Calculator
Find the minimum copper gas pipe diameter for an appliance load and pipe run, to keep the pressure drop within 1 mbar (BS 6891).
Undersized gas pipework starves an appliance and fails a tightness/working-pressure check. Enter the total appliance load in kW and the length of the pipe run, and this calculator converts the load to a gas flow rate and returns the minimum copper pipe size (15, 22 or 28mm) that keeps the pressure drop within the 1 mbar allowance from BS 6891.

Gas Pipe Sizing Calculator results
Fill in the details and select Calculate to see your figures.
Win more of the jobs you quote.
Tradehand is the software your trade business runs on, with an assistant that answers every call and message, sends your quotes the same day and chases them until they land. The first £10,000 Tradehand collects for a business carries no Tradehand fee. After that, Tradehand earns 5% of collected invoice payments. No monthly fee, setup fee, card fee or contract.
Get startedHow to use the Gas Pipe Sizing Calculator
- 1Enter the total gas load in kW of the appliance(s) the pipe will feed: add them up if the run supplies more than one.
- 2Enter the length of the pipe run from the meter to the appliance. Allow extra for bends and fittings, which add resistance.
- 3Read the gas flow in m³/hr and the minimum copper pipe size that keeps the drop within 1 mbar.
- 4Remember the 1 mbar allowance is for the WHOLE installation. A long run in a smaller pipe may need stepping up, or splitting the allowance across sections.
How the Gas Pipe Sizing Calculator works
Sizing gas pipe is a two-step job: convert the load to a flow rate, then look up the smallest pipe that can carry it over your run length without exceeding the 1 mbar drop.
- 30 kW combi ÷ 10.76 = 2.79 m³/hr.
- At a 6m run, BS 6891 gives 15mm = 1.9 m³/hr (too small) and 22mm = 5.8 m³/hr (ample).
- So use 22mm copper for a 30kW combi on a 6m run.
- At a 3m run, 15mm carries 2.9 m³/hr, so a short run could take 15mm. Length is decisive.
Guide values based on BS 6891 for copper at a 1 mbar drop and relative density 0.6; verify against the current BS 6891 standard for the specific installation. Uses kW ÷ 10.76 (net CV basis). Gas work must be carried out by a Gas Safe registered engineer.
Typical UK benchmarks
| Pressure drop allowance | ≤1 mbar total across the installation: BS 6891 |
| 15mm copper at 6m | max 1.9 m³/hr at 1 mbar: BS 6891 Table 2 |
| 22mm copper at 6m | max 5.8 m³/hr at 1 mbar: BS 6891 Table 2 |
| kW → m³/hr | divide kW by 10.76 (natural gas) |
Disclaimer
This tool gives an estimate for general guidance only, based on typical UK figures and the details you enter. It is not a formal quote, survey, or professional advice. Always confirm with a qualified tradesperson before relying on any figure, as regional prices, site conditions, and current standards vary.
You do the job, Tradehand handles everything around it.
Your assistant sends the quotes, chases the invoices, books the work and keeps your customers updated. The first £10,000 Tradehand collects for a business carries no Tradehand fee. After that, Tradehand earns 5% of collected invoice payments. No monthly fee, setup fee, card fee or contract. One office hire costs about £25,000 a year, whether the invoices land or not.