Best Voltage Tester UK: Two-Pole Testers And Proving Units For Electricians

The best voltage tester for safe isolation: Martindale and Fluke two-pole testers, proving units, what GS38 says, and how they differ from multimeters.
Blake Folgado, Co-founder, Tradehand9 min read
Clay illustration of an electrician in blue overalls holding an insulated screwdriver beside a consumer unit and four spare screwdriver bits

What is the best voltage tester for electricians?

For proving a circuit dead, buy a two-pole voltage tester sold with its own proving unit. HSE's GS38 guidance says to use a proprietary test lamp or a 2-pole voltage detector, rather than a multimeter, to establish whether voltage is present, and to prove the device before and after use. Martindale's VIPD138-S and VT28PD-S kits and Fluke's T150 are three UK options, covered below with the figures on each maker's page.

A non-contact voltage stick is a different tool. GS38 says it is only for identifying live equipment, never for proving it dead.

Key takeaways

  • Martindale VIPD138-S: the VI13800 indicator plus a PD440S proving device in one kit. The page lists it as GS38 compliant, CAT III 1000V and CAT IV 600V.
  • Martindale VT28PD-S: a VT28 two-pole tester (10 to 690V on its LED and LCD range) with continuity and phase rotation, sold with a PD690S proving unit.
  • Fluke T150: 6 to 690V, continuity to 400 kilohms, designed to IEC EN 61243-3:2014. Fluke's page does not list a proving unit, so buy one separately.
  • Multimeters measure. GS38 does not recommend them for detecting voltage.
  • Non-contact sticks such as the Martindale NC2 detect a live conductor. They do not prove one dead.

Sources: HSE: GS38 Electrical test equipment for use on low voltage electrical systems (fourth edition, 2015), Martindale: VIPD138-S voltage indicator and proving device kit, Martindale: VT28PD-S voltage tester and proving unit kit, Fluke UK: T150 two-pole voltage and continuity electrical tester, Martindale: NC2 non-contact voltage tester

Voltage tester comparison: four testers side by side

TesterTypeVoltage range on the pageRatingProving unit
Martindale VIPD138-S kit (VI13800)Two-pole indicatorAC and DC in four stages, 50V to 400VCAT III 1000V, CAT IV 600VPD440S in the kit
Martindale VT28PD-S kit (VT28)Two-pole tester12 to 690V AC/DC (LED), 10 to 690V (LED and LCD)CAT III 1000V, CAT IV 600VPD690S in the kit
Fluke T150Two-pole tester6 to 690V AC/DCCAT IV 600V, CAT III 690VNot listed on the page
Martindale NC2Non-contact detector200 to 1000V AC, 40 to 400HzNot statedNot applicable

Sources: Martindale: VIPD138-S voltage indicator and proving device kit, Martindale: VT28PD-S voltage tester and proving unit kit, Fluke UK: T150 two-pole voltage and continuity electrical tester, Martindale: NC2 non-contact voltage tester

What GS38 and the HSE guidance say about proving dead

The Electricity at Work Regulations 1989 require adequate precautions to prevent electrical equipment that has been made dead from becoming charged again during the work (regulation 13). HSE's FAQ adds that where work is on or near exposed conductors, they should be proven dead, using appropriate test equipment, before work starts. HSG85, HSE's safe working practices guidance, covers planning that work. HSE's FAQ says to isolate securely, apply a lock to each isolation device and post warning notices at the points of isolation. GS38 then asks you to prove the tester on the proving unit, test the circuit and prove the tester again.

GS38 (fourth edition, 2015) is the test-equipment guidance. The points that decide what you buy:

  • Use the right detector (paragraph 19): to establish the presence or absence of voltage, use a proprietary test lamp or 2-pole voltage detector suitable for the working voltage, rather than a multimeter. HSE says incorrectly set multimeters and makeshift devices have often caused accidents.
  • Prove the detector (paragraph 20): any device used to prove dead may fail to indicate danger, so prove it before and after use, preferably on a voltage proving unit. Some devices have built-in proving units. Otherwise use a known live source of similar voltage.
  • Two-pole detectors (paragraph 12): a 2-pole voltage detector that conforms to BS EN 61243-3 does not need extra current-limiting resistors or HBC fuses.
  • Non-contact sticks (paragraph 13): voltage sticks are for identifying live equipment, not for proving it dead. Only devices that make contact with the conductor should be used for proving dead.
  • Probes (paragraph 9): leads and probes should be marked with their CAT rating and the maker's name, with finger barriers and no more than 4mm of exposed metal tip. HSE strongly recommends 2mm or less, or spring-loaded retractable screened probes.

Sources: HSE: GS38 Electrical test equipment for use on low voltage electrical systems (fourth edition, 2015), HSE: GS38 publication page, HSE: Electricity at work FAQs (making equipment safe to work on), HSE: HSG85 Electricity at work: Safe working practices (third edition), legislation.gov.uk: Electricity at Work Regulations 1989, regulation 13

Martindale VIPD138-S and VT28PD-S kits

Martindale VIPD138-S is a safe isolation kit: the VI13800 voltage indicator, a PD440S proving unit and a TC71 carry case. The page lists AC and DC indication in four stages from 50V to 400V, suitability for safe isolation procedures up to 600V, a CAT III 1000V and CAT IV 600V rating, and says it is GS38 compliant. The PD440S is described as a 440V AC proving device designed to enable voltage indicators to be fully checked. Listed features include retractable probes, heavy-duty finger guards and a cable with a white inner core that shows damage. The warranty is 2 years.

Martindale VT28PD-S is a VT28 two-pole voltage tester, a PD690S proving unit and a TC72 case. The page lists 12 to 690V AC/DC on the LED range and 10 to 690V on the combined LED and LCD range, continuity with a buzzer, phase rotation, a single-pole test and an LED torch. It states the kit fully meets the requirements of GS38 and proving dead procedures, with a CAT III 1000V and CAT IV 600V rating and a 2-year warranty.

The proving unit checks the indicator, not the circuit. That is the before-and-after proving step GS38 paragraph 20 asks for.

Sources: Martindale: VIPD138-S voltage indicator and proving device kit, Martindale: VT28PD-S voltage tester and proving unit kit, HSE: GS38 Electrical test equipment for use on low voltage electrical systems (fourth edition, 2015)

Fluke T150

Fluke T150 is a two-pole voltage and continuity tester. Fluke's page lists 6 to 690V AC/DC, a CAT IV 600V and CAT III 690V safety rating, continuity from 0 to 400 kilohms and resistance up to 1999 ohms. Voltage is shown by LED, LCD, audible tone or tactile feedback. It weighs 180g and carries a 2-year warranty.

Fluke says it is designed according to IEC EN 61243-3:2014 to verify the absence of voltage, even with discharged batteries. GS38 refers to BS EN 61243-3 for 2-pole detectors. The Fluke UK page does not mention GS38 by name or list a proving unit, so pair it with a separate proving unit and check the tip protection you will use against GS38 paragraph 9.

Sources: Fluke UK: T150 two-pole voltage and continuity electrical tester, HSE: GS38 Electrical test equipment for use on low voltage electrical systems (fourth edition, 2015)

Non-contact testers: useful, but not for proving dead

Martindale NC2 detects AC voltage between 200V and 1000V at 40 to 400Hz, with a red LED at the tip, a buzzer and an LED torch. It is optimised for 230V single and 3-phase supplies. The page describes detecting the presence of voltage and does not claim it proves a circuit dead.

That matches GS38, which says non-contact or proximity detectors can be useful for indicating that something is live, for example when removing one cable from trunking holding many, but only contact devices should be used for proving dead.

Sources: Martindale: NC2 non-contact voltage tester, HSE: GS38 Electrical test equipment for use on low voltage electrical systems (fourth edition, 2015)

Voltage tester, multimeter or continuity tester?

  • Two-pole voltage tester: detects voltage for safe isolation. It is the tool GS38 names for proving dead, used with a proving unit.
  • Multimeter: measures voltage, current and resistance. GS38 notes that unsuitable leads, a wrong function setting or a voltage above the meter's limit can cause arcing, and recommends fused leads (usually not exceeding 500mA, HBC) when a multimeter is used.
  • Continuity function on a two-pole tester: a quick check on a dead circuit. The Fluke T150 page lists continuity to 400 kilohms and resistance to 1999 ohms, and the Martindale VT28 lists a continuity buzzer. These pages describe voltage and continuity testers, not multifunction installation testers.
  • Fused leads and resistance: GS38 warns that low-current fuses can add up to 2 ohms to a test lead, which matters when you use fused leads with resistance measuring equipment.

Sources: HSE: GS38 Electrical test equipment for use on low voltage electrical systems (fourth edition, 2015), Fluke UK: T150 two-pole voltage and continuity electrical tester, Martindale: VT28PD-S voltage tester and proving unit kit

What should you check before buying a voltage tester?

  • Two-pole, with a proving unit: a kit that includes the proving unit saves buying one separately.
  • Standard: GS38 refers to BS EN 61243-3 for 2-pole detectors. Check the maker's page names it, or says GS38 compliant.
  • Category rating: the rating should suit the supply you work on. The Martindale and Fluke testers above list CAT IV 600V.
  • Voltage range: confirm the range covers the supply. The VI13800 indicates 50V to 400V in four stages.
  • Probe tips: no more than 4mm exposed, ideally 2mm or less or retractable.
  • Prove before and after every use: a faulty tester can fail to indicate danger, which is why GS38 asks you to prove it.

For the rest of the kit, see the essential electrician tools guide and the best torque screwdriver for electricians. For the legal side, see the health and safety guide for electrician businesses.

Sources and references

Blake Folgado

Blake is a co-founder of Tradehand, a UK trades marketplace More from Blake

Frequently asked questions

Can I use a multimeter to prove a circuit dead?

GS38 says to use a proprietary test lamp or a 2-pole voltage detector rather than a multimeter to establish the presence or absence of voltage, because incorrectly set multimeters have often caused accidents.

What is a proving unit?

A proving unit is a known voltage source used to check the voltage tester works. GS38 says to prove the device before and after use, preferably on a voltage proving unit. The Martindale VIPD138-S and VT28PD-S kits each include one.

Can a non-contact voltage stick prove a circuit dead?

No. GS38 says single-pole and non-contact detectors should only be used to identify live equipment, and that only devices that make contact with the conductor should be used for proving dead.

How much probe tip can be exposed under GS38?

GS38 says no more than 4mm of exposed metal tip, with 2mm or less strongly recommended where practicable, or spring-loaded retractable screened probes.

Is the Fluke T150 GS38 compliant?

Fluke's UK page says it is designed according to IEC EN 61243-3:2014 and does not mention GS38 by name. GS38 refers to BS EN 61243-3 for 2-pole voltage detectors. Check the probe tips and proving method you use against GS38 itself.

Get on with the work.

Spend less time on admin and more on the work you love.

A clay decorator rolling sage green paint onto a living room wall
A clay carpenter hanging an oak internal door
A clay tiler taking a phone payment from a homeowner after a job
A clay plasterer smoothing a bedroom wall with a trowel
A clay electrician testing a socket in a living room
Two clay tradespeople sharing a business card beside an open van