Skip to main content
EICR C2 Meaning: Potentially Dangerous, Fix It Urgently

EICR C2 Meaning: Potentially Dangerous, Fix It Urgently

Not sure? We'll check for you.

C2 on an EICR means potentially dangerous: urgent remedial action is required and the report is unsatisfactory until it is done.

Medium

Updated

What's happening?

C2 on an EICR means potentially dangerous, and Electrical Safety First's classification guide says urgent remedial action is required. It is the second most serious code, after C1 (danger present, immediate action). One C2 anywhere is enough to make the whole report unsatisfactory, which is why a house can fail with an otherwise tidy installation. A C2 is a defect that is not an immediate danger today but would become one if something else went wrong, such as a fault current with no RCD to switch the circuit off. It is different from C3, an improvement recommendation that does not fail the report, and from FI, which means the inspector could not tell and further investigation is needed. A C2 should be put right promptly, and for rented homes in England the law sets a deadline.

What usually causes it?

  • No RCD protection on a socket that could feed mobile equipment used outdoors
  • No RCD protection on a socket-outlet in a room with a bath or shower
  • The main RCD failing to trip when the inspector tests it
  • Earthing or bonding conductors missing, undersized or not connected
  • Damaged or overheated wiring, accessories or consumer unit
  • A circuit where the protective device would not disconnect quickly enough in a fault

Is it dangerous?

A C2 is potentially dangerous, not an emergency. The installation is usable in the meantime, but the defect means a fault could cause shock or fire without the protection you would expect. Do not leave it for months, and tell the electrician straight away if anything gets warm, smells or trips.

Can I fix it myself?

No. Remedial work on a C2 means testing and often changes to the consumer unit or circuit protection, which needs a competent electrician. What you can do is read the report, find the item numbers coded C2, and ask for each one to be explained in plain words.

When should you call an electrician?

As soon as the report arrives, send it to an electrician and ask for a quote on every C2 and any FI. For a landlord in England the remedial work must be completed within 28 days, or sooner if the report says so. A homeowner has no set deadline, but the code says urgent.

What will the electrician actually do?

  • Go through each C2 item and show where it is on site
  • Quote for the remedial work, usually protection devices, earthing and bonding or a consumer unit
  • Carry out the work and test the affected circuits
  • Issue an Electrical Installation Certificate or minor works certificate for it
  • Confirm in writing that the C2 items are cleared, as a landlord must supply

Who fixes this

What it usually costs

EICR Cost
£100–£330
Fuse Box Replacement Cost
£500–£1,500 for a three-bed semi

Questions people ask

What does C2 mean on an EICR?

C2 means potentially dangerous, with urgent remedial action required. It makes the EICR unsatisfactory, unlike C3, which is only a recommendation.

How long do I have to fix a C2 on an EICR?

For a landlord in England, remedial work must be done within 28 days of the report, or sooner if the report says so. For an owner-occupier there is no fixed legal deadline, but the code means urgent, so book the work now rather than at the next convenient time.

Is a C2 a fail on an EICR?

Yes. Any C1 or C2 makes the report unsatisfactory. FI items must still be investigated, and C3 items do not fail it.

What are examples of a C2 on an EICR?

The classification guide lists, for example, no RCD protection for mobile equipment likely to be used outdoors, no RCD for a socket in a bath or shower location, and a main RCD that fails to operate when tested.

Sources & References

  1. Electrical Safety First: Best Practice Guide 4, EICR classification codes
  2. IET Wiring Matters: EICR myths
  3. GOV.UK: Electrical safety standards in the private and social rented sectors